Product Status Discontinued on 8/3/2020

Overview

The PDU3V602D354 17.3kW 3-Phase Vertical PDU Outlet Strip is a required accessory option for Tripp Lite’s PDU360AT6G60 and other 3-phase ATS PDUs that specify compatibility with this model. It’s recommended for high-density equipment racks in data centers, server rooms and heavily configured equipment racks.

When used with the PDU360AT6G60, the PDU3V602D354 supports up to 17.3kW total output with 27.8A balanced maximum full load per output phase combination (L1–L2, L2–L3, L3–L1) and 13.9A balanced maximum per breakered output load bank (C1–C6).

The 54 single-phase 12A 208V IEC-C13 outlets receive power from the connected ATS PDU. The outlets are interlaced to help you balance loads by spreading connections across the phase combinations throughout the rack. Each outlet is numbered and color-coded to help you keep track of connected devices and which phase combination powers each. Dual 2.5-foot power cords, each with a special eight-position plug, connect directly to the PDU’s rear receptacles.

The PDU3V602D354’s rugged all-metal housing mounts in compatible racks with no tools needed. Vertical 0U installation reduces cord clutter and improves airflow through the rack.

Features

Required Accessory for Select Tripp Lite ATS PDUs
  • Compatible with PDU360AT6G60 and other select Tripp Lite 3-phase ATS PDUs
  • Recommended for high-density equipment racks in data centers and server rooms
  • Saves rack space, improves airflow and reduces cord clutter by locating outlets closer to connected devices
  • Supports up to 17.3kW total output with 27.8A maximum per output phase combination and 13.9A max per breakered output load bank
  • Heavy-duty 2.5 ft. power cords with proprietary 8-position plugs connect to ATS PDU

54 C13 Interlaced 208V Outlets
  • Single-phase 12A IEC-C13 outlets help balance loads by spreading connections across phase combinations (L1–L2, L2–L3, L3–L1) throughout the rack
  • Numbered and color-coded for easy ID of connected devices and which phase combination powers them
  • 20A double-pole magnetic circuit breakers protect against overload

Installs Easily in 0U of Rack Space
  • Preinstalled mounting buttons for toolless vertical rack-mounting in compatible racks
  • Preinstalled grounding lug for connecting devices that require chassis ground
  • Heavy-duty all-metal housing provides durability in demanding rack environments

Package Includes

  • PDU3V602D354 17.3kW 3-Phase Vertical PDU Outlet Strip, 54 C13 Outlets
RoHS compliant

Specifications

OVERVIEW
UPC Code037332192493
Accessory Type0U Strip for 3-Phase ATS PDU
Accessory ClassPDU Accessories
DISPLAY
Accessories (Included)Mounting hardware
INPUT
Input Phase3-Phase
Maximum Input Amps48
Maximum Input Amps Details48A total 208V 3 Phase input (24A max per input cord)
Input Cord DetailsIncludes 7 conductor input plug for use with compatible Tripp Lite ATS PDU products only
Input Cord Length (ft.)2.5
OUTPUT
Output Capacity DetailsSupports up to 17.3kW total output; 27.8A max per output phase (L1-L2, L2-L3, L3-L1), 13.9A max per breakered output load bank (C1-C6) when used with Tripp Lite's PDU360AT6G60 ATS; All configurations: 12A max per C13 outlet
Frequency Compatibility50 / 60 Hz
Output Receptacles(54) C13
Output Nominal Voltage200; 208; 220; 230; 240
PHYSICAL
Material of ConstructionMetal
Form Factors SupportedVertical rackmount installation supported with toolless mounting in button-mount compatible racks
PDU Form FactorVertical (0U)
Shipping Dimensions (hwd / in.)7.28 x 7.68 x 79.53
Shipping Weight (lbs.)24.97
Unit Dimensions (hwd / in.)70.000 x 4.000 x 2.170
Unit Weight (lbs.)19
ENVIRONMENTAL
Operating Temperature Range0 to 50C (32 to 122F)
Storage Temperature Range-15C to 60C (5 to 140F)
Relative Humidity5-95% non-condensing
Operating Elevation0-10,000
WARRANTY & SUPPORT
Product Warranty Period (Worldwide)2-year limited warranty

Questions & Answers

Accessories

Power Cords and Adapters

  Model Number Description
PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 2 ft. (0.61 m), Black P004-002-13A P004-002-13A PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 2 ft. (0.61 m), Black
PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 3 ft. (0.91 m), Black P004-003-13A P004-003-13A PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 3 ft. (0.91 m), Black
PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 4 ft. (1.22 m), Black P004-004-13A P004-004-13A PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 4 ft. (1.22 m), Black
PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 5 ft. (1.52 m), Black P004-005-13A P004-005-13A PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 5 ft. (1.52 m), Black
PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 6 ft. (1.83 m), Black P004-006-13A P004-006-13A PDU Power Cord, C13 to C14 - 13A, 250V, 16 AWG, 6 ft. (1.83 m), Black
Heavy-Duty PDU Power Cord, C13 to Left-Angle C14 - 15A, 250V, 14 AWG, 6 ft. (1.83 m), Black P005-006-14LA P005-006-14LA Heavy-Duty PDU Power Cord, C13 to Left-Angle C14 - 15A, 250V, 14 AWG, 6 ft. (1.83 m), Black
Heavy-Duty PDU Power Cord, C13 to Right-Angle C14 - 15A, 250V, 14 AWG, 6 ft. (1.83 m), Black P005-006-14RA P005-006-14RA Heavy-Duty PDU Power Cord, C13 to Right-Angle C14 - 15A, 250V, 14 AWG, 6 ft. (1.83 m), Black

Need help with your purchase?
We're always available to help with questions, including product selection, sizing, installation and product customization. Call us at +1 773-869-1776 or email cpdipresaleshelp@eaton.com.