Comparing 2 Products


SV100KL

SmartOnline SV Series 100kVA Large-Frame Modular Scalable 3-Phase On-Line Double-Conversion 208/120V 50/60 Hz UPS System

More Info
How to Order
On-Line
SV100KL 100kVA Configuration: 300A; Maximum 140kVA Large Chassis Configuration: 420A; 330A maximum inrush current
120/208V 3-PH Wye; 127/220V 3-PH Wye
Set of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, G) inputs from two separate power sources
Hardwire
MAIN and ALTERNATE AC inputs are each protected by 630A 3 pole magnetic breakers
3-Phase
40 to 70Hz (online mode); 50/60Hz Auto-selectable
0.99 (full load)
Less than 3% (full linear load)
100000
100
90000
90
OVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1 minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to 100% or less
0.9
3:1
Output THD full resistive load: <1.5%; Output THD non-linear load: <4%; Max DC offset: ±50mV; Max Phase angle deviation: 2°; Max Voltage unbalance deviation: 1%; Output short-circuit protection included
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Auto-selectable, user adjustable
Output wiring: 3P, N, E
630A 3 pole magnetic breaker
Pure Sine wave
Pure Sine wave
120/208V 3-PH Wye; 127/220V 3-PH Wye
Hardwire
ONLINE, FREQUENCY CONVERSION, BATTERY MODE: 208/120, 220/127 ±1% typical (balanced load); ±2% typical (unbalanced load); ECONOMY MODE: 208/120, 220/127 ±15V; BYPASS MODE: +15% (default, adjustable to +10%, +15% or +20%), -20% (default, adjustable to -10%, -20%, -30%)
ONLINE MODE: Output frequency is ±0.05Hz of input frequency when input is within ±4Hz* of the configured 50/60Hz output setting; Output frequency is ±0.05Hz the configured 50/60Hz output setting when input is outside ±4Hz* of the configured 50/60Hz output setting; BATTERY MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; FREQUENCY CONVERTER MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; ECONOMY MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (UPS switches to Online mode if frequency goes outside of this range); BYPASS MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (switches to STANDBY mode if frequency goes outside of this range). *The TRACKING RANGE is factory set to ±4Hz and is user adjustable to ±1Hz, ±2Hz or ±4Hz; The selected TRACKING RANGE setting controls frequency output tolerances as described above in Online, Economy and Bypass modes
Output Amp Capacity 278A (208/120V); 262A (220/127V)
No
Includes 5 SV20PM 20kVA power modules. Up to 3 additional SV20PM 20kVA power modules can be added for additional capacity or N+1 availability; Add 1 SV20PM for 120kVA capacity (or 100kVA with N+1 redundancy); Add 2 SV20PM for 140kVA capacity (or 120kVA with N+1 redundancy); Add 3 SV20PM for 140kVA total capacity with N+1 redundancy
Batteries sold separate; Runtime is dependent on battery pack quantity and load level
Supports extended runtime with optional external battery packs; 500A 3 pole 250VDC breaker recommended for external battery
Yes
External battery pack wiring is contractor supplied
 BP240V370 ;  BP240V370NB ;  EBP240V2502 ;  EBP240V2502NB ;  EBP240V3502 ;  EBP240V3502NB ;  EBP240V5001 ;  EBP240V5001NB ;  EBP240V5002 ;  EBP240V5002NB ;  EBP240V6002 ;  EBP240V6002NB ;  EBP240V6003 ;  EBP240V6003NB 
±120VDC
User selectable charging current of 1A to 40A (2A factory setting); Recharge rate is dependent on number of external battery packs connected and the selected charge current setting
Hot-swappable, replaceable batteries
Online, double-conversion power conditioning
Maintains continuous output in online mode, without using battery power, during overvoltages to 253V (Ph-Ph), reducing output to within 1% of selected 208/120V, 220/127V nominal output voltage
Maintains continuous output in online mode, without using battery power, during brownout/undervoltage conditions to 156V (Ph-Ph) at full load and to 121V (Ph-Ph) at 70% output load or less, increasing output to within 1% of selected 208/120V or 220/127V nominal output voltage
145mm front panel LCD display with directional scroll and select buttons offers complete operating status display, plus setting and selection options for all UPS functions
Front panel buttons include ESC (menu escape), UP/LEFT (menu up / left), DOWN/RIGHT (menu down / right), ENTER (confirm selection), HOME (return to home screen) and POWER (on/off power control); Also includes Manual Bypass switch
Audible alarms can be muted using on-screen prompts
Unique audible alarms for POWER ON / POWER OFF (alarm sounds for 2 seconds), BATTERY MODE (alarm sounds every 2 seconds), LOW BATTERY (alarm sounds every 0.5 seconds), UPS ALARM (alarm sounds every 1 second), UPS FAULT (continuous alarm)
Front panel LED indicators represent INPUT (green), BYPASS (amber), INVERTER (green), BATTERY (red) and ALARM (red)
Yes
2496
2496 joules (Ph-Ph), 2496 joules (Ph-N), 1872 joules (N-E)
Instantaneous
Tower
Fans
Tower
1,100
2,010
600
Steel
79.13 x 23.62 x 43.3
445.88
983
0° to +40°C (+32° to +104°F); De-rates to 90% capacity at 35°C / 95°F and 80% capacity at 40°C / 104°F
-15° to +60°C (+5° to +140°F)
0 to 95%, non-condensing
29484
2134
99%
Less than 73 DBA front-side, 1m
Up to 1000m (At elevations over 1000m, output de-rates by 1% per 100m)
 WEBCARDLX ;  MODBUSCARDSV ;  RELAYCARDSV 
Includes pre-installed Tripp Lite WEBCARDLX network interface
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert
DB9 cabling included
Includes pre-installed  WEBCARDLX  network interface card
DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface
No transfer time (0 ms.) in online, double-conversion mode; Less than 20 ms. transfer time in economy mode
Maintains continuous operation without using battery power during brownout/undervoltage conditions to to 156V (Ph-Ph) Full load or 121V (Ph-Ph) 70% load or less; Below the low transfer voltage point, output is maintained utilizing reserve battery power
Maintains continuous operation without using battery power during overvoltages to 253V (Ph-Ph), reducing output within 1% of nominal; Above this point, output is maintained utilizing reserve battery power
Cold-start operation supported
Automatic inverter bypass; Hot swappable batteries; Hot swappable UPS power module; Auto Probe Monitoring (included); Zero transfer time; On-Line/Double-Conversion
Greater than 95% efficiency - GREEN UPS; High efficiency economy mode operation; Schedulable daily hours of economy mode operation
ROHS (Restriction of Hazardous Substances); Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
UL1778: 2014 5th Edition; CSA C22.2 No. 107.3.14; FCC Part 15 Class A
1-year limited warranty
2-year limited warranty
1-year limited warranty
2-year limited warranty
Tripp Lite 3-Phase UPS Factory Warranty
SV120KL

SmartOnline SV Series 120kVA Large-Frame Modular Scalable 3-Phase On-Line Double-Conversion 208/120V 50/60 Hz UPS System

More Info
How to Order
On-Line
SV120KL 120kVA Configuration: 360A; Maximum 140kVA Large Chassis Configuration: 420A; 330A maximum inrush current
120/208V 3-PH Wye; 127/220V 3-PH Wye
Set of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, G) inputs from two separate power sources
Hardwire
MAIN and ALTERNATE AC inputs are each protected by 630A 3 pole magnetic breakers
3-Phase
40 to 70Hz (online mode); 50/60Hz Auto-selectable
0.99 (full load)
Less than 3% (full linear load)
120000
120
108000
108
OVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1 minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to 100% or less
0.9
3:1
Output THD full resistive load: <1.5%; Output THD non-linear load: <4%; Max DC offset: ±50mV; Max Phase angle deviation: 2°; Max Voltage unbalance deviation: 1%; Output short-circuit protection included
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Auto-selectable, user adjustable
Output wiring: 3P, N, E
630A 3 pole magnetic breaker
Pure Sine wave
Pure Sine wave
120/208V 3-PH Wye; 127/220V 3-PH Wye
Hardwire
ONLINE, FREQUENCY CONVERSION, BATTERY MODE: 208/120, 220/127 ±1% typical (balanced load); ±2% typical (unbalanced load); ECONOMY MODE: 208/120, 220/127 ±15V; BYPASS MODE: +15% (default, adjustable to +10%, +15% or +20%), -20% (default, adjustable to -10%, -20%, -30%)
ONLINE MODE: Output frequency is ±0.05Hz of input frequency when input is within ±4Hz* of the configured 50/60Hz output setting; Output frequency is ±0.05Hz the configured 50/60Hz output setting when input is outside ±4Hz* of the configured 50/60Hz output setting; BATTERY MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; FREQUENCY CONVERTER MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; ECONOMY MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (UPS switches to Online mode if frequency goes outside of this range); BYPASS MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (switches to STANDBY mode if frequency goes outside of this range). *The TRACKING RANGE is factory set to ±4Hz and is user adjustable to ±1Hz, ±2Hz or ±4Hz; The selected TRACKING RANGE setting controls frequency output tolerances as described above in Online, Economy and Bypass modes
Output Amp Capacity 333A (208/120V); 315A (220/127V)
No
Includes 6 SV20PM 20kVA power modules. Up to 3 additional SV20PM 20kVA power modules can be added for additional capacity or N+1 availability; Add 1 SV20PM for 140kVA capacity (or 120kVA with N+1 redundancy); Add 2 SV20PM for 140kVA capacity with N+1 redundancy
Batteries sold separate; Runtime is dependent on battery pack quantity and load level
Supports extended runtime with optional external battery packs; 600A 3 pole 250VDC breaker recommended for external battery
Yes
External battery pack wiring is contractor supplied
 BP240V370 ;  BP240V370NB ;  EBP240V2502 ;  EBP240V2502NB ;  EBP240V3502 ;  EBP240V3502NB ;  EBP240V5002 ;  EBP240V5002NB ;  EBP240V6002 ;  EBP240V6002NB ;  EBP240V6003 ;  EBP240V6003NB 
±120VDC
User selectable charging current of 1A to 48A (2A factory setting); Recharge rate is dependent on number of external battery packs connected and the selected charge current setting
Hot-swappable, replaceable batteries
Online, double-conversion power conditioning
Maintains continuous output in online mode, without using battery power, during overvoltages to 253V (Ph-Ph), reducing output to within 1% of selected 208/120V, 220/127V nominal output voltage
Maintains continuous output in online mode, without using battery power, during brownout/undervoltage conditions to 156V (Ph-Ph) at full load and to 121V (Ph-Ph) at 70% output load or less, increasing output to within 1% of selected 208/120V or 220/127V nominal output voltage
145mm front panel LCD display with directional scroll and select buttons offers complete operating status display, plus setting and selection options for all UPS functions
Front panel buttons include ESC (menu escape), UP/LEFT (menu up / left), DOWN/RIGHT (menu down / right), ENTER (confirm selection), HOME (return to home screen) and POWER (on/off power control); Also includes Manual Bypass switch
Audible alarms can be muted using on-screen prompts
Unique audible alarms for POWER ON / POWER OFF (alarm sounds for 2 seconds), BATTERY MODE (alarm sounds every 2 seconds), LOW BATTERY (alarm sounds every 0.5 seconds), UPS ALARM (alarm sounds every 1 second), UPS FAULT (continuous alarm)
Front panel LED indicators represent INPUT (green), BYPASS (amber), INVERTER (green), BATTERY (red) and ALARM (red)
Yes
2496
2496 joules (Ph-Ph), 2496 joules (Ph-N), 1872 joules (N-E)
Instantaneous
Tower
Fans
Tower
1,100
2,010
600
Steel
79.13 x 23.62 x 43.3
479.90
1058
0° to +40°C (+32° to +104°F); De-rates to 90% capacity at 35°C / 95°F and 80% capacity at 40°C / 104°F
-15° to +60°C (+5° to +140°F)
0 to 95%, non-condensing
35558
2673
99%
Less than 73 DBA front-side, 1m
Up to 1000m (At elevations over 1000m, output de-rates by 1% per 100m)
 WEBCARDLX ;  MODBUSCARDSV ;  RELAYCARDSV 
Includes pre-installed Tripp Lite WEBCARDLX network interface
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert
DB9 cabling included
Includes pre-installed  WEBCARDLX  network interface card
DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface
No transfer time (0 ms.) in online, double-conversion mode; Less than 20 ms. transfer time in economy mode
Maintains continuous operation without using battery power during brownout/undervoltage conditions to to 156V (Ph-Ph) Full load or 121V (Ph-Ph) 70% load or less; Below the low transfer voltage point, output is maintained utilizing reserve battery power
Maintains continuous operation without using battery power during overvoltages to 253V (Ph-Ph), reducing output within 1% of nominal; Above this point, output is maintained utilizing reserve battery power
Cold-start operation supported
Automatic inverter bypass; Hot swappable batteries; Hot swappable UPS power module; Auto Probe Monitoring (included); Zero transfer time; On-Line/Double-Conversion
Greater than 95% efficiency - GREEN UPS; High efficiency economy mode operation; Schedulable daily hours of economy mode operation
ROHS (Restriction of Hazardous Substances); Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
UL1778: 2014 5th Edition; CSA C22.2 No. 107.3.14; FCC Part 15 Class
1-year limited warranty
2-year limited warranty
1-year limited warranty
2-year limited warranty
Tripp Lite 3-Phase UPS Factory Warranty
Clear List

CONTACT US

Phone

Sales
Mon - Fri 8 AM - 5:30 PM CST
+1 (773) 869-1776

Support
Mon - Fri: 8 AM - 5:30 PM CST
+1 (773) 869-1234

Tripp Lite
1111 West 35th Street
Chicago, Illinois 60609
United States

+1 (773) 869-1111 Main
1 773.869.1329 Fax

Business Hours
8 AM - 5:30 PM CST

See all contact options

Need help with your purchase?
We're always available to help with questions, including product selection, sizing, installation and product customization. Call us at +1 (773) 869-1776 or email presaleshelp@tripplite.com.