Voltage Incompatibility
This product is not compatible with the voltage in your country. [MP004]
SmartOnline S3MX Series 3-Phase 380/400/415V 40kVA 36kW On-Line Double-Conversion UPS, Parallel for Capacity and Redundancy, Single & Dual AC Input, No Internal Batteries
Model Number: S3M40KXD-NIB New
- Best-in-class footprint and power density minimize space requirements for up to 40kVA
- Intuitive LCD interface offers key performance, configuration and diagnostics info
- High efficiency (94% on-line, 98% ECO mode) helps reduce operating costs
- Optional WEBCARDLX network management card allows cost-effective remote management
- Parallel for capacity and redundancy up to 3 units
- Single and dual AC input capability
- 2-year limited warranty
Features
Typical Applications
- Save space in tight data center environments with best-in-class small footprint
- Back up essential equipment in network, telecom, financial and edge infrastructure applications
- Maintain critical server-room operations during all power conditions, including short blackouts
Package Includes
- S3M40KXD-NIB SmartOnline S3MX Series 3-Phase 380/400/415V 40kVA 36kW On-Line Double-Conversion UPS (No Internal Batteries)
- RS-232 cable
- Paralleling cable kit
- Owner’s manual
Specifications
OVERVIEW
UPC Code | 037332239785 |
UPS Type | On-Line |
OUTPUT
Output Volt Amp Capacity (VA) | 40000 |
Output kVA Capacity (kVA) | 40.00 |
Output Watt Capacity (Watts) | 36000 |
Output kW Capacity (kW) | 36.00 |
Power Factor | 0,9 |
Crest Factor | 3:1 |
Frequency Compatibility | 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion |
Frequency Compatibility Details | Automatic frequency selection |
Output Voltage Regulation (Line Mode) | +/- 1% |
Output Voltage Regulation (Economy Line Mode) | +/-11V of nominal |
Output Voltage Regulation (Battery Mode) | +/- 1% |
Output AC Waveform (AC Mode) | Pure Sine wave |
Output AC Waveform (Battery Mode) | Pure Sine wave |
Output Capacity Details | Supports up to 100% load continuously in double conversion mode; Supports 100-110% load for 10 minutes, 110 to 130% load for 1 minute and greater than 130% for 1 second before switching to bypass mode; Inverter mode is automatically restored as load levels are reduced to less than 70%; Configuration options support up to 3 S3M40KX-NIB systems wired in parallel for increased capacity or fault-tolerant, redundant operation |
Nominal Output Voltage(s) Supported | 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye |
Output Receptacles | Hardwire |
Individually Controllable Load Banks | No |
INPUT
Rated input current (Maximum Load) | 61A |
Nominal Input Voltage(s) Supported | 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye |
Nominal Input Voltage Description | 3-Phase Wye, 4 wire plus ground (L1, L2, L3, N, G) |
UPS Input Connection Type | Hardwire |
Input Circuit Breakers | 80A (3 pole) |
Input Phase | 3-Phase |
Power Factor (Input) | .99PF (100% load) |
THDi | <3% (100% load) |
BATTERY
Expandable Battery Runtime | Supports extended runtime with optional external battery packs |
External Battery Pack Compatibility | BP480V09 ; BP480V10 ; BP480V10 -NIB; BP480V100 ; BP480V100 -NIB; BP480V40 ; BP480V40 -NIB; BP480V65 ; BP480V65 -NIB |
DC System Voltage (VDC) | +/- 240 |
Battery Recharge Rate (Included Batteries) | 9 hours to 90% (Internal batteries) |
Expandable Runtime | Yes |
VOLTAGE REGULATION
Voltage Regulation Description | Online, double-conversion power conditioning maintains output within 1% of the selected nominal voltage in online mode |
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display | LCD DISPLAY: offers a variety of graphical, text and numeric information to indicate a wide range of UPS operation and fault / warning conditions, including current operating mode, alarm status, load level, battery charge, input / output voltage & frequency, estimated runtime and more (see user manual for a detailed listing) |
Switches | ON / ENTER BUTTON: turns the UPS on and confirms a selection from the settings menu; OFF / ESC BUTTON: turns off the UPS and returns to the previous item in the settings menu; TEST / UP BUTTON: initiates UPS self-test operation and advances to the next item in the settings menu; MUTE / DOWN BUTTON: silences the audible alarm and advances to the previous item in the settings menu; Press TEST/UP & MUTE/DOWN buttons simultaneously for 1 second to enter or exit the settings menu (See user manual for detailed information) |
Audible Alarm | Alarms warn users of a variety of operational conditions: BYPASS MODE (beeps every 2 seconds), BATTERY MODE (beeps every 4 seconds), FAULT MODE (beeps continuously), OVERLOAD (beeps twice per second), OTHER WARNINGS (beeps once per second), FAULT (beeps continuously); All alarms can be silenced, except OVERLOAD & OTHER WARNINGS conditions |
LED Indicators | 4 LEDs report BYPASS / LINE / BATTERY / FAULT modes |
PHYSICAL
Cooling Method | Fans |
Installation Form Factors Supported with Included Accessories | Tower |
Primary Form Factor | Tower |
Primary UPS Depth (mm) | 815 |
Primary UPS Height (mm) | 1,000 |
Primary UPS Width (mm) | 300 |
Shipping Dimensions (hwd / in.) | 47.44 x 16.90 x 36.22 |
UPS Housing Material | Steel |
UPS Power Module Dimensions (Height x Width x Depth, mm) | 1000 x 300 x 815 |
UPS Power Module Dimensions (hwd, in.) | 39.37 x 11.81 x 32.08 |
UPS Power Module Weight (kg) | 80.29 |
UPS Power Module Weight (lbs.) | 177.0 |
ENVIRONMENTAL
Operating Temperature Range | 0 to +40C (32-104F) |
Storage Temperature Range | 0 to +35C (32 to 95F) with battery; -15 to 60C (5 to +140F) without battery |
Relative Humidity | 5 to 95%, non-condensing |
Operating Elevation (ft.) | < 3280ft (Capacity de-rates by 1% for every 328ft over 3280ft ) |
Audible Noise | <60dBA at 1meter |
Operating Elevation (m) | < 1000m (Capacity de-rates by 1% for every 100m over 1000m) |
COMMUNICATIONS
Communications Interface | DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
Network Management Cards | WEBCARDLX ; MODBUSCARDSV ; RELAYCARDSV |
Network Monitoring Port Description | Card accessory slot supports network management interface or programmable I/O relay card options |
Communications Cable | DB9/RS-232 cable included |
LINE / BATTERY TRANSFER
Transfer Time | Zero transfer time Online to Battery, Inverter to Bypass 0ms (Synchronous), and Inverter to ECO mode < 10ms. |
Low Voltage Transfer to Battery Power (Setpoint) | 120V (Ph-N), 208V (Ph-Ph) @50% load / 176V (Ph-N), 305V (Ph-Ph) @100% load |
High Voltage Transfer to Battery Power (Setpoint) | 276V (Ph-N), 478V (Ph-Ph) @ 50% or 100% load. |
SPECIAL FEATURES
Grounding Lug | Yes |
Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported |
High Availability UPS Features | Automatic inverter bypass; Manual bypass switch |
Green Energy-Saving Features | High efficiency economy mode operation |
CERTIFICATIONS
UPS Certifications | CE |
UPS Certification Details | IEC/EN 62040-1:2008+A1 (Safety); IEC/EN 62040-2:2006 (Category C3) |
WARRANTY
Product Warranty Period (International) | 2-year limited warranty |
Accessories
Model Number | Description | |
---|---|---|
![]() |
BP480V09 | External UPS Battery Pack, 80 9Ah Batteries Included - S3M30KX S3MX-Series 3-Phase UPS System |
![]() |
BP480V10 | External UPS Battery Pack, 80 10Ah Batteries Included - S3M40KX S3MX-Series 3-Phase UPS System |
![]() |
BP480V10-NIB | External UPS Battery Pack, 80 10Ah for S3M40KX or 80 9Ah for S3M30KX , No Batteries Included - S3M30KX or S3M40KX 3-Phase UPS System |
![]() |
BP480V100 | External UPS Battery Pack, 40 100Ah Batteries Included - Compatible S3MX-Series 3-Phase UPS System |
![]() |
BP480V100-NIB | External UPS Battery Pack, 40 100Ah, No Batteries Included - Compatible S3MX-Series 3-Phase UPS System |
![]() |
BP480V40 | External UPS Battery Pack, 40 40Ah Batteries Included - Compatible S3MX-Series 3-Phase UPS System |
![]() |
BP480V40-NIB | External UPS Battery Pack, 40 40Ah, No Batteries Included - Compatible S3MX-Series 3-Phase UPS System |
![]() |
BP480V65 | External UPS Battery Pack, 40 65Ah Batteries Included - Compatible S3MX-Series 3-Phase UPS System |
![]() |
BP480V65-NIB | External UPS Battery Pack, 40 65Ah, No Batteries Included - Compatible S3MX-Series 3-Phase UPS System |
Model Number | Description | |
---|---|---|
![]() |
SU40KMBPKX | 3 Breaker Maintenance Bypass Panel for SVT30KX, SVX30_, S3M30KX, SU40KX |
Model Number | Description | |
---|---|---|
![]() |
WEBCARDLX | Web Management Accessory Card |
![]() |
E2MT | EnviroSense2 (E2) Environmental Sensor Module, Temperature |
![]() |
E2MTDO | EnviroSense2 (E2) Environmental Sensor Module with Temperature and Digital Outputs |
![]() |
E2MTHDI | EnviroSense2 (E2) Environmental Sensor Module with Temperature, Humidity and Digital Inputs |
![]() |
MODBUSCARDSV | Programmable RS-485 Management Accessory Card for Select 3-Phase UPS Systems |
![]() |
RELAYCARDSV | Programmable Relay I/O Card for Tripp Lite SVTX, SVX, S3MX and SV UPS Systems |
Customers Who Viewed This Item Also Considered
Start-Up Services
WNNDNN1NGB
Emergency Service for Single-Phase or 3-Phase UPS in Great Britain - Normal Business Hours
Add to Favorites More... Ordering HelpWNNDNN2NGB
Emergency Service for Single-Phase or 3-Phase UPS in Great Britain - Off Business Hours
Add to Favorites More... Ordering HelpWNNDNN3NGB
Emergency Service for Single-Phase or 3-Phase UPS in Great Britain - Weekend
Add to Favorites More... Ordering HelpW3BNBANNGB
Annual Service Agreement for 40-90K 3-Phase UPS in Great Britain - Bronze (1 PM)
Add to Favorites More... Ordering HelpW3BNGANNGB
Annual Service Agreement for 40-90K 3-Phase UPS in Great Britain - Gold (1 PM)
Add to Favorites More... Ordering HelpW3BNSANNGB
Annual Service Agreement for 40-90K 3-Phase UPS in Great Britain - Silver (1 PM)
Add to Favorites More... Ordering HelpW3BRBANNGB
Annual Service Agreement for 40-90K 3-Phase UPS in Great Britain - Bronze (2 PM)
Add to Favorites More... Ordering HelpW3BRGANNGB
Annual Service Agreement for 40-90K 3-Phase UPS in Great Britain - Gold (2 PM)
Add to Favorites More... Ordering HelpW3BRSANNGB
Annual Service Agreement for 40-90K 3-Phase UPS in Great Britain - Silver (2 PM)
Add to Favorites More... Ordering HelpW3FSNN1NGB
Commissioning for 10-80K 3-Phase UPS in Great Britain - Normal Business Hours
Add to Favorites More... Ordering HelpResources & Downloads
Documentation
Product Literature
Declarations of Conformity
Product Images
How can we improve the information on this page?
Is an important specification missing? Did you spot an error? Please let us know how we can make this information more useful to you.